
Clamp-On Flow Sensor
FD-H series
Flow Sensors Standard model 25A/32AFD-H32
Specifications
Model |
FD-H32 |
|||
Type |
Standard model |
|||
Supported pipe diameter |
1" (25A), ø28–37ø1.10"-1.46" |
|||
Supported pipe materials |
Metal piping, hard plastic piping*1 |
|||
Supported fluids |
All fluids (water, oil, chemicals, etc.)*1 |
|||
Supported fluid temperature |
0–85°C32–185°F(no freezing on pipe surface)*2 |
|||
Maximum rated flow |
1" (25A) : 200 L/min52.8 gal/min |
|||
Zero cut flow rate |
1.0 L/min0.3 gal/min(variable, initial value) |
|||
Detection principle |
Delta TOF + Pulse Doppler |
|||
Function for automatic correction for speed of sound in liquid |
Yes |
|||
Display |
QVGA 2.0 model: color LCD, status indicator light |
|||
Display update cycle |
Approx. 10 times/second |
|||
Display resolution |
Instantaneous flow |
0.01/0.1/1 (L/min) (default value: 1) |
||
Integrated flow |
0.01/0.1/1 (L) (default value: 1; up to 8 digits) |
|||
Response time |
0.5 s / 1.0 s / 2.5 s / 5.0 s / 10.0 s / 30.0 s / 60.0 s / 120.0 s / 200.0 s |
|||
Measurement accuracy |
Between 10 and 100% of F.S.: ±3.0% of RD*3*4 |
|||
Repeatability |
0.5 s: ±1.0%, 1 s: ±0.7%, 2.5 s: ±0.45%, 5 s: ±0.3%, 10 s: ±0.2%, 30 s: ±0.15%, 60 s: ±0.1% of F.S.*3*5 |
|||
Hysteresis |
Variable |
|||
Flow units |
L/min m3/h G/min |
|||
Pulse output increments (L) |
0.02–999.99 |
|||
Pipe temperature measurement accuracy |
±2.0°C±3.5°F(pipe temperature 0–50°C32–122°F) , ±3.0°C±5.4°F(pipe temperature 50–85°C122–185°F) (ambient temperature of 25°C77°F)*3 |
|||
Network support |
IO-Link*6 |
|||
Heat calculation function |
Unit |
MJ/h kW kBTU/h*7 |
||
Display resolution |
Instantaneous value (MJ/h): 0.01/0.1/1 (default value 0.1); Integrated value (MJ): 0.01/0.1/1 (default value 0.1)*7 |
|||
Pulse output increments (MJ) |
0.02–999.99*7 |
|||
Data accumulation |
Accumulation period |
Approx. 1 year |
||
Data reading |
USB2.0 |
|||
Power I/O connector |
M12 8-pin connector (male) |
|||
I/O (switchable) |
Output (Ch1/2/3/4) |
Instantaneous flow mode / area mode / pulse output mode / integrated flow mode / bubble detection mode / error output |
||
模拟输出(Ch1/2) |
4–20 mA/0–20 mA (switchable), load resistance 500 Ω or less |
|||
External input (Ch2/3) |
Integrated reset input / flow-rate zero input / zero-point adjustment input / bank input |
|||
Power supply |
Power voltage |
20–30 VDC, ripple (P-P) 10% included, Class 2/LPS |
||
Current consumption |
240 mA or less (when using flow sensor standalone; with analog output; excluding load current)*8 |
|||
Protection circuit |
Protection against reverse power connection, power supply surges, output short circuits, and output surges |
|||
Environmental resistance |
Enclosure rating |
IP65/67 (IEC 60529)*9 |
||
Ambient temperature |
Sensor head: −20 to +60°C–4 to +140°F(no freezing); Display unit: −20 to +50°C–4 to +122°F(no freezing)*2 |
|||
相对湿度 |
35–85% RH (no condensation) |
|||
Vibration resistance |
10–500 Hz; Power spectral density: 0.816 G2/Hz; X, Y and Z directions |
|||
Shock resistance |
100 m/s2(approx. 10 G), 16 ms pulses, 1000 times each for X, Y and Z axes |
|||
Material |
Display unit |
Body: PPS/PET/POM; Display window: PAR |
||
Sensor head |
Body: PPS/PET/PAR/SUS304 |
|||
Weight |
approx. 620 g21.87 oz |
|||
*1佛r fluids through which ultrasonic waves propagate, and which do not contain a large quantity of bubbles. Detection may be unstable depending on the type and condition of the pipe. |
||||

